TRICONEX 2401 digital output module
The TRICONEX 2401 is a digital output module designed for early-generation Triconex safety and control systems, primarily used to convert digital control signals from Triconex controllers into electrical signals that drive field actuators. It serves as a critical "execution link" for safety interlock logic and process control commands, ensuring reliable operation of on-site equipment in industrial scenarios. Below is its comprehensive detailed information:
The TRICONEX 2401’s primary role is to receive digital control instructions (e.g., "open/close valve," "start/stop pump," "activate alarm") from Triconex controllers and output corresponding electrical signals to drive field actuators such as solenoid valves, contactors, indicator lights, and relays. It is widely applied in:
- Safety-critical scenarios: Executing emergency shutdown (ESD) commands (e.g., closing isolation valves when pressure exceeds limits) and safety interlock actions (e.g., stopping feed pumps if reactor temperature is abnormal).
- Routine process control: Controlling the on/off status of common industrial equipment (e.g., conveyor belts, dosing pumps) and activating status indicators (e.g., "equipment running" green lights, "fault alert" red lights).
- Output Type: Dry contact output (relay output) or solid-state output (configurable based on specific models, adapting to different load types).
- Nominal Output Voltage: 24V DC (mainstream industrial voltage); supports 18–32V DC wide voltage input to tolerate fluctuations in on-site power supplies.
- Output Current Capacity:
- Continuous output current: 1A per channel (sustained stable operation for long-term driven loads like small solenoid valves).
- Inrush current: 5A (10ms duration, handling start-up current surges of inductive loads such as contactors).
- Minimum Load Current: 10mA (ensuring reliable switching of low-power devices like indicator lights without false cutoff due to insufficient load).
- Leakage Current: <1mA (max, preventing unintended activation of sensitive actuators caused by residual current).
- Isolation Rating: Galvanic isolation between output channels and between channels and system ground; isolation voltage is 250V AC (channel-to-channel, 1 minute) and 500V AC (channel-to-ground, 1 minute), effectively eliminating cross-interference between channels and ground loop issues.
- Overcurrent & Short-Circuit Protection: Built-in self-recovering fuses or current-limiting circuits per channel; if a channel experiences a short circuit (e.g., field wiring fault), the module automatically limits current to ≤50mA to prevent component burnout, and triggers a fault alarm.
- Overvoltage Protection: Each channel withstands 150V DC continuous overvoltage or 250V AC short-term (1 second) overvoltage, resisting transient voltage spikes from on-site wiring or load switching.


The company has multiple main brands, and if you have other brand requirements, you can also send them to customer service for inquiry.